86
3x0041 Htg pump cmd 0-1 Off*On
3x0042 El htg outp signal 0 - 100%
3x0043 El heating cmd 0-1 Off*On
3x0044 Heat pump Cooling 0 - 100%
3x0045 Heat pump 0 - 100%
3x0046 Heat pump state 0-2 None*Cooling*Heating
3x0047 Heat pump Heating 0 - 100%
3x0048 Heat pump (heating) 0-1 None*Heating
3x0049 El htg 2 outp sign 0 - 100%
3x0050 El heating 2 cmd 0-1 Off*On
3x0051
3x0052 Humidification 0 - 100%
3x0053 Humidification (state) 0-1 Off* On
3x0054
3x0055 Dehumidification 0 - 100%
3x0057
3x0058
3x0059
3x0060 Alarm output 0-1 Normal*Alarm
3x0061
3x0062
3x0064 Act airquality comp 0 - 100%
3x0065 Act fan clg value 0 - 100%
3x0066 Act fan htg value 0 - 100%
3x0067 Act fan comp tmp 0 - 100%
3x0068 Current fan speed compensation (humidity) 0 - 100%
3x0069
3x0070
3x0071 Current mixing compensation (humidity) 0 - 100%
3x0072 Outside air temp `-x.y - +x.y °C (factor 10)
3x0073 Supply air temp `-x.y - +x.y °C (factor 10)
3x0074 Heating frost tmp °C (factor 10)
3x0075 Valid room tmp °C (factor 10)
3x0076 Return air temp °C (factor 10)
3x0077 Exhaust air temp °C (factor 10)
Input register (Read) (continuation)
Connection to the Master System (ModBus Standard)
Adress Description Values/Units Remarks

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Remak VCS and is the answer not in the manual?

Remak VCS Specifications

General IconGeneral
BrandRemak
ModelVCS
CategoryControl Unit
LanguageEnglish