What to do if there is no flame during operation in my REMEHA Quinta Pro 45?
R
Robyn MaldonadoSep 2, 2025
If there's no flame during operation of your REMEHA Boiler, here's what you can check:
* Vent the gas supply to remove any air.
* Ensure the gas valve is fully opened and verify the gas supply pressure.
* Check the operation and setting of the gas valve unit.
* Make sure the air supply inlet and flue gas outlet are not blocked.
* Ensure there is no recirculation of flue gases.
D
Dennis ParksSep 3, 2025
Why is the maximum flow temperature exceeded in my REMEHA Boiler?
M
Michelle HarveySep 3, 2025
If the maximum flow temperature is exceeded in your REMEHA Boiler, it could be due to no flow or insufficient flow. Check the flow (direction, pump, valves) and reasons for the heat demand.
A
Anna LongSep 3, 2025
Why is the maximum difference between the flow and return temperature exceeded in my REMEHA Quinta Pro 45 Boiler?
B
Brian MelendezSep 4, 2025
If the maximum difference between the flow and return temperature has been exceeded in your REMEHA Boiler, it may be due to no flow or insufficient flow. You should check the flow (direction, pump, valves). Also, check the water pressure and ensure the heat exchanger is clean.