19
UEZ-IOM (07-23) 1034347-I
Supply Piping Connections
Install a ground joint union and manual shutoff valve upstream of the unit control system, as shown in Figure 10.
The 1/8-inch plugged tapping in the manual shutoff valve in Figure 10 provides connection for a supply line
pressure test gauge.
The National Fuel Gas Code requires the installation of a trap with a minimum 3-inch drip leg (see Figure 10).
Local codes may require a drip leg longer than 3 inches (typically 6 inches). To permit burner removal, this drip
leg must extend beyond the edge of the heater.
Leak-test all connections by brushing on a leak-detecting solution. Bleed trapped air from gas lines as needed.
The gas connection is made at the pipe nipple that extends outside the cabinet, as shown in Figure 10. Gas
connection sizes are listed in Table 14.
Table 14. Gas Connection Sizes
Unit Size
Natural Gas Propane
Connection (Inches)*
130, 180 1/2 1/2
260, 310 3/4 3/4
*Connection size for a standard unit (not gas supply line size).
Figure 10. Gas Connections
Vent Connections
NOTE: IMPORTANT: For unit sizes 055, 085, and 110, install the venting system in accordance
with the venting system manufacturer’s instructions. For unit sizes 130, 180, 260, and 310, install
the venting system in accordance with the following paragraphs.

Table of Contents

Other manuals for Reznor APD

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Reznor APD and is the answer not in the manual?

Reznor APD Specifications

General IconGeneral
BrandReznor
ModelAPD
CategoryGas Heater
LanguageEnglish

Related product manuals