EasyManua.ls Logo

Rheem Raypak AVIA 264 - Page 8

Rheem Raypak AVIA 264
188 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8
U.S. Installations
1
Canadian Installations
2
A
Clearance above grade, veranda, porch, deck, or
balcony
1' (30 cm) 1' (30 cm)
B Clearance to window or door that may be opened
4' (1.2 m) below or to side of
opening
3' (91 cm)
C Clearance to permanently closed window
* *
D
Vertical clearance to ventilated so󰀩t located above the
terminal within a horizontal distance of 2' (61 cm) from
the centerline of the terminal
5' (1.5 m)
*
E Clearance to unventilated so󰀩t
* *
F Clearance to outside corner
* *
G Clearance to inside corner 6' (1.83 m)
*
H
Clearance to each side of center line extended above
meter/regulator assembly
*
3' (91 cm) within a height
15' (4.5 m) above the meter/
regulator assembly
I Clearance to service regulator vent outlet
*
6' (1.83 m)
J
Clearance to non-mechanical air supply inlet to
building or the combustion air inlet to any other
appliance
4' (1.2 m) below or to side of
opening; 1' (30 cm) above
opening
3' (91 cm)
K Clearance to mechanical air supply inlet
3' (91 cm) above if within
10' (3 m) horizontally
6' (1.83 m)
L
Do not terminate above paved sidewalk or paved
driveway
Slip hazard due to frozen
condensate
Slip hazard due to frozen
condensate
M Clearance under veranda, porch, deck or balcony
*
1' (30 cm)
t
1
In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
2
In accordance with the current CAN/CSA-B149 Installation Codes.
t
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor and top of terminal, and underside
of veranda, porch, deck or balcony is greater than 1' (30 cm).
* Clearances in accordance with local installation codes and the requirements of the gas supplier.
A
INSIDE
CORNER DETAIL
V = VENT
X = AIR INLET
F10692
V
G
H
A
B
B
V
V
B
B
V
A
J
X
I
M
V
X
K
V
V
B
F
C
OPERABLE
FIXED
CLOSED
FIXED
CLOSED
OPERABLE
Table C. Vent/Air Inlet Termination Clearances
Figure 3. Minimum Clearances from Vent/Air Inlet Terminations – Indoor and Outdoor Installations

Table of Contents

Related product manuals