44
8. OPERATING
INSTRUCTIONS
Before Start-Up
Burners
Keep heater area clear and free from combustibles,
ammable liquids and chemicals. Do not obstruct the ow
of combustion and ventilation air.
Water
Water must be owing through the heater during operation.
Ensure that the system is lled with water and that the
pump is operating. The heater should always have a
minimum of 40 GPM (151 lpm) water owing through it.
Start-Up Procedures
Your pool and spa heater has been designed for years of
safe and reliable pool/spa water heating. It is available with
electronic ignition only. This manual provides installation,
operation, maintenance, and service information for these
heaters.
MODESERVICE
DOWN
UP
CONNECT
LCD DISPLAY TEMP ADJUST CONNECT MENU
SERVICE MENU MODE KEY
ON / OFF
SWITCH
Figure 71. Heater Control Toggle Switch
If your heater has been installed correctly, operating the
heater is an easy task. The upper front panel of the heater
contains the control center that allows you to turn the
heater On or O and adjust the temperature settings for
the pool or spa. The temperature range is factory-set from
65°F (18°C) to 104°F (40°C). See Figure 71 for location of
toggle switch to turn the heater On and O.
See "Controls" section on page 27 for additional details
about the use of the controls in the Control Adjustments
subsection.
After Start-Up
Feel the inlet and outlet pipes. Outlet pipe should be only
slightly warmer than the inlet. It should not be hot.
A
WARNING: Should overheating occur or the gas
supply fail to shut o, turn o the manual gas control to
the appliance.
A
AVERTISSEMENT: En cas de surchaue ou
si l’alimentation en gaz ne s’arrete pas, fermez
manueiiement ie robinet d’arret de l’admission de gaz.
Water Pressure Switch
A water pressure switch is provided in the heater to shut o
the burners in the event that water supply is interrupted. It
is very important to verify that the switch electrically opens
and shuts o the gas valve when water ow to the heater is
interrupted. Otherwise, rapid and severe damage will likely
occur to the heater.
The water pressure switch should be checked and adjusted
for proper operation by a qualied service person at the
time of installation and periodically checked thereafter.
Refer to "Water Pressure Switch Adjustment" on page
38.
F10671
Figure 72. Water Pressure Switch
A
WARNING: Operation of the heater without water
circulation will cause rapid and severe damage to the
heater, which will not be covered under warranty.