What does it mean when Riello UPS display shows A30, A32 and the CPS does not start up?
- MmarymasonSep 8, 2025
If the Riello UPS display shows codes A30 or A32 and the CPS does not start up, it could be due to: * Ambient temperature < 0°C. Heat the environment, wait for the heat sink temperature to rise above 0°C and then start up the CPS. * Fault in heat sink temperature probe. Activate the maintenance bypass (SWMB) if present, turn the CPS off and back on again and exclude the maintenance bypass. If the problem persists, contact the nearest service centre.