Questions and Answers

  • H
    Hannah AguirreSep 8, 2025
    What does it mean when Riello UPS display shows A30, A32 and the CPS does not start up?
    • M
      marymasonSep 8, 2025
      If the Riello UPS display shows codes A30 or A32 and the CPS does not start up, it could be due to: * Ambient temperature < 0°C. Heat the environment, wait for the heat sink temperature to rise above 0°C and then start up the CPS. * Fault in heat sink temperature probe. Activate the maintenance bypass (SWMB) if present, turn the CPS off and back on again and exclude the maintenance bypass. If the problem persists, contact the nearest service centre.
  • K
    Kimberly SalinasAug 23, 2025
    What to do if Riello UPS display shows nothing or provides incorrect information?
    • K
      Kimberly GibsonAug 23, 2025
      If the Riello UPS display shows nothing or provides incorrect information, the display may have power supply problems. To resolve this, activate the maintenance bypass (SWMB), completely shut down the CPS and wait a few seconds. Turn the CPS back on and check if the display operates normally. If the fault persists, contact the nearest technical support centre.
  • S
    Sara CabreraAug 25, 2025
    Why Riello UPS connected to the mains does not switch to stand by mode?
    • K
      kimberly15Aug 25, 2025
      If your Riello UPS, connected to the mains, does not switch to standby mode (and the display does not light up), consider the following potential causes: * A missing connection to the input terminal. Connect the mains to the terminals following the indications in the paragraph “POWER CONNECTION”. * A missing neutral connection. Connect the mains to the terminals as explained in the paragraph “POWER CONNECTION”. * The isolator (SWIN) is open. Close the isolator. * Mains power missing (blackout). Make sure the mains power is present. If necessary, perform battery start-up to power the load. * Intervention of the upstream protection device. Restore the protection. Warning: make sure there is no overload or short circuit on the CPS output.
  • V
    vbryantAug 26, 2025
    What does code A26 mean on Riello UPS?
    • J
      Joseph HuberAug 26, 2025
      If the Riello UPS display shows the code A26, it indicates that the battery fuses are blown or the fuse holder isolators are open. Replace the fuses or close the battery fuse holder isolator (SWBATT). If necessary, replace fuses with others of the same type.
  • L
    Lynn Wade MDAug 27, 2025
    What does code C05 mean on Riello UPS?
    • L
      Luis OwensAug 27, 2025
      If the Riello UPS display shows the code C05, it could be due to: * Maintenance bypass switch (SWMB) closed. Open the manual bypass switch (SWMB). * The jumper is missing from the terminals “SWITCH BYPASS”. Insert the jumper.
  • M
    Marissa GallegosSep 23, 2025
    What does code L11 mean on Riello UPS?
    • S
      Sean ScottSep 23, 2025
      If the Riello UPS display shows the code L11, it indicates a static bypass rupture or fault. To resolve this, activate the maintenance bypass (SWMB) if present. Turn the CPS off and back on again. Exclude the maintenance bypass and if the problem persists, contact the nearest service centre.
  • T
    timothyspearsSep 16, 2025
    What does it mean when Riello UPS display shows L01, L10, L38, L39, L41?
    • C
      castroaudreySep 16, 2025
      If the Riello UPS display shows one or more of the following codes: L01, L10, L38, L39, L41, it indicates a fault in: temperature probe or CPS cooling system, main auxiliary power supply, or static bypass switch. Activate the maintenance bypass (SWMB) if present, turn the CPS off and back on again. Exclude the maintenance bypass. If the problem persists, contact the nearest service centre.
  • B
    Bobby WarrenSep 18, 2025
    What does code F03, A08 mean on Riello UPS?
    • M
      michelledownsSep 18, 2025
      If the Riello UPS display shows the codes F03 or A08, it means that internal protection fuses on the phase or on the input relay are broken. Contact the nearest service centre.
  • T
    Tiffany TylerSep 6, 2025
    What to do if Riello UPS display is off, the fans are off but the load is powered?
    • T
      Tyler MorrisonSep 6, 2025
      If the Riello UPS display is off, the fans are off, but the load is powered, there may be a fault in the auxiliary power supplies and the CPS is in bypass supported by the redundant power supply. Activate the maintenance bypass (SWMB) if present. Switch off the CPS, wait for a minute and turn the CPS back on. If the display does not turn on or if the sequence fails, contact the nearest service centre, leaving the CPS in manual bypass mode.
  • J
    Jennifer ArellanoSep 3, 2025
    What does code C01 mean on Riello UPS?
    • A
      Annette Holmes DVMSep 4, 2025
      If the Riello UPS display shows the code C01, the jumper is missing from the R.E.P.O. connector or it is not inserted correctly. Assemble the jumper or make sure that it is inserted correctly.