What to do if no power reaches the load with Riello UPS?
- Ddiana25Aug 22, 2025
If no power reaches the load when using a Riello UPS, check the following: * Ensure the load is properly connected to the output terminals. * Verify the CPS is not in standby mode by running the start-up sequence. * Confirm the operating mode; the STAND-BY OFF mode only powers loads during a blackout. If this mode is selected, change the operating mode. * If the CPS is malfunctioning and the automatic bypass is out of use, insert the maintenance bypass (SWMB) and contact the nearest service center.