Start-up, calibration and operation of the burner
8.6 Final checks
– Block the flame sensor and turn off the remote controls: the
burner must start and then stop in lockout after approximately
5 s after ignition.
– Free the flame sensor and turn off the remote controls: the
burner must stop in lockout.
– Block the flame sensor when the burner is operating: the
flame must turn off and the burner stop in lockout within 1 s.
– Turn on the remote control TL followed by TS while the
burner is operating: the burner must stop.
Make sure that the mechanical locking systems
on the adjustment devices are fully tightened.