EasyManua.ls Logo

Riello Array AR 800 - APPENDIX F - TROUBLESHOOTING TABLE

Riello Array AR 800
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
53
SHUTDOWN
53
APPENDIX
APPENDIX
Disconnect the multimeter and reconnect the wires, as
shown in the picture below.
1 (NC)
2 (NO)
3 (COM)
Fig. 69
Wired pressure switch
Test the pressure switch on the other side of the boiler
(module 4 or 8); repeat the process from Fig. 66 through
Fig. 69.
If the multimeter shows “0” (or any other symbol conrming the
electrical continuity between 1 (NC) and 3 (COM) of the air pressure
switch), the error on the boiler is due to a lack of water on the
hydraulic circuit (or a failure of the pressure switch itself).
If the multimeter shows the air pressure switch circuit between
1 (NC) and 3 (COM) is open, the error is due to an air pressure
differential between boiler cabinet and boiler room higher than
1.4”wc (or a failure of the pressure switch itself).
The root cause is most likely an obstruction/blockage on
combustion air inlet.

Table of Contents

Related product manuals