Technical description of the burner
13
20036644
GB
3.8 Firing rates
Maximum output must be selected in the hatched area of the dia-
gram (Fig. 5).
Minimum output must not be lower than the minimum limit shown
in the diagram.
WARNING
The firing rate area values have been obtained con-
sidering an ambient temperature of 68 °F, and an
atmospheric pressure of 394” WC and with the
combustion head adjusted as shown on page 28.
Model MBtu/hr
RLS 300/E 4,732
RLS 400/E 6,817
RLS 500/E 9,468
RLS 650/E 11,362
RLS 800/E 13,256
0
2
4
6
8
10
12
14
16
18
20
mb a r
22
9
8
7
6
5
4
3
2
0
1
w.c.
0
5600
5200
4800
4400
4000
3600
32002800
2400
2000
1600
1200
800
400
0
6000
9200
8800
8400
8000
7600
72006800
6400
MBtu / h
kW
2000 4000 6000 8000 10000 12000 14000 16000 18000 20000 22000 24000 26000 28000 30000
Fig. 5
D11255
RLS 650/E RLS 800/E
0
2
4
6
8
10
12
14
16
18
20
mb ar
8
7
6
5
4
3
2
0
1
w.c.
0
5600
5200
4800
4400
4000
3600
32002800
2400
2000
1600
1200
800
400
0
6000
MBtu / h r
kW
2000 4000 6000 8000 10000 12000 14000 16000 18000 20000
RLS 300/E RLS 400/E RLS 500/E
Burner power output
Combustion chamber pressure
Firing rate for C-ETL Canadian Listing
Firing rate for C-ETL Canadian Listing
Burner power output
Combustion chamber pressure
D11254