Start-up, calibration and operation of the burner
43
20036644
GB
5.7.4 Low oil pressure switch
The low oil pressure switch (Fig. 49) is factory set to 261 PSI (18
bar).
If the oil pressure goes down this value in the delivery piping, the
pressure switch stops the burner.
Burner starts again automatically if the pressure goes above
261 PSI (18 bar) after burner start up.
-
+
-
Fig. 49
D10627