8-4 MEASURING INSULATION RESISTANCE
Use a “Dr. Robin” generator tester in megger tester
mode or use a megger tester to check the insula-
tion resistance. Remove the control panel, and
disconnect the connector of GREEN lead for
ground. Connect a megger tester to one of re-
ceptacle output terminals and the ground termi-
nal, then measure the insulation resistance. An
insulation resistance of 1 megohm or more is nor-
mal. (The original insulation resistance at the time
of shipment from the factory is 10 megohm or
more.) If it is less than 1 megohm, disassemble
the generator and measure the insulation resis-
tance of the stator, rotor and control panel indi-
vidually.
NOTE : Turn on the no-fuse breaker before mea-
surement.
* STATOR
(1) Measure the insulation resistance between
BLUE lead and the core.
(2) Measure the insulation resistance between
WHITE lead and the core.
(3) Measure the insulation resistance between
BROWN lead and the core.
* ROTOR
Measure the insulation across one of the soldered
terminals of the rotor and the core.
Fig. 8-10
Fig. 8-11
Fig. 8-12