Rockwell Automation Publication 1756-UM004C-EN-P - June 2021 11
Chapter 1 ControlLogix EtherNet/IP Network Device Overview
1756-EN3TR 3.6 or later
18.02.0
0 or later
(4)
2.56 or later
25,000
(5)
2000 No
Up to 128 axes
supported
(5)
1756-EN4TR Any
24.00.00 or later
(6)
4.10 or later
50,000 without
CIP Security
25,000 with
integrity
15,000 with
integrity and
confidentiality
3,700 without CIP
Security
2,700 with
integrity
1,700 with
integrity and
confidentiality
No
Up to 256 axes
supported
(5)
1756-EN4TRXT Any
24.00.00 or later
(6)
4.10 or later
50,000 without
CIP Security
25,000 with
integrity
15,000 with
integrity and
confidentiality
3,700 without CIP
Security
2,700 with
integrity
1,700 with
integrity and
confidentiality
Yes
Up to 256 axes
supported
(5)
(1) Includes the K conformal coating catalog numbers.
(2) I/O numbers are maximums; they assume no HMI/MSG. HMI/MSG numbers are maximums, they assume no I/O. Packet rates vary depending on packet size. For more details, see
Troubleshoot EtherNet/IP Application Technique, publication ENET-AT003
, and the EDS file for a specific catalog number.
(3) Module operates in a broad temperature spectrum, -20…70 ºC (-4…158 ºF), and meets ANSI/ISA-S71.04-1985 Class G1, G2 and G3, as well as cULus, Class 1 Div 2, C-Tick, CE, ATEX Zone 2 and
SIL 2 requirements for increased protection against salts, corrosives, moisture/condensation, humidity, and fungal growth.
(4) This version is required to use CIP Sync™ technology, Integrated Motion on the EtherNet/IP Network, or Exact Match keying.
(5) This value assumes the use of a1756-L8x or a 1756-L7x ControlLogix controller. For a 1756-L6x ControlLogix controller, see ControlLogix Controllers User Manual, publication 1756-UM001
.
(6) CIP Security requires FactoryTalk Linx version 6.11.00 or later.
Table 4 - ControlLogix EtherNet/IP Specifications
(1)
Cat. No.
Firmware
Revision
RSLogix 5000
Software Version
RSLinx Software
Version
Packet Rate Capacity (packets/
second)
(2)
Support for
Extended
Environment
(3)
Integrated Motion on
the EtherNet/IP
Network Axes
I/O HMI/MSG

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley ControlLogix 1756-EN2F and is the answer not in the manual?

Rockwell Automation Allen-Bradley ControlLogix 1756-EN2F Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley ControlLogix 1756-EN2F
CategoryNetwork Hardware
LanguageEnglish

Related product manuals