Chapter 11 Application References
Configure the Digital Output for Brake Control
1. Determine whether logic of the brake control circuit is ‘Active High’ or
‘Active Low’.
‘Active High’ control sets or engages the brake when the signal is energized.
‘Active Low’ control sets or engages the brake when the signal is de-
energized.
2. Navigate to the port that contains the IO option card.
For example, navigate to port 4 when using a 20-750-2262C-2R in slot 4.
3. Configure the digital output selector to receive control from the correct
bit in the Torque Prove status word.
For example, when using Relay Output 0 on the 20-750-2262C-2R in slot
4 to control the brake, go to parameter 4:10 [RO0 Sel]:
For ‘Active High’ control, set the value to 9:52 [Trq Prove Status] bit 4
‘Brake Set’
or
For ‘Active Low’ control, set the value to 9:52 [Trq Prove Status] bit 8
‘BrakeRelease’.
Configure the Torque Prove Function
1. Navigate to port 9, which is the port for Application Control.
2. Navigate to parameter 9:50 [Trq Prove Cfg]. Set bit 0 ‘TP Enable’.
3. Then set bit 6 ‘BrkSlipStart’.
4. Navigate to the following parameters and enter the data for the crane
application.
Confirm Configuration
1. Check brake control.
2. Run the crane up and down without load.
3. Run the crane up and down with load.
4. If necessary, adjust the acceleration and deceleration times.
9:53 [Trq Lmt SlewRate] 9:54 [Speed Dev Band] 9:55 [SpdBand Intgrtr]
9:60 [Brk Release Time] 9:61 [Brk Set Time] 9:62 [Brk Alarm Travel]
9:63 [Brk Slip Thresh] 9:64 [Brake Test Torq] 9:68 [DI Brake Fdbk]
9:70 [Float Tolerance] 9:71 [MicroPsnScalePct] 9:72 [ZeroSpdFloatTime]
9:78 [DI FloatMicroPsn]
10/11:1915 [VRef Accel Time1] 10/11:1917 [VRef Decel Time1]