Rockwell Automation Publication 750-IN017B-EN-P - June 2018 3
PowerFlex 750-Series Service Cart Frames 8…10 Conversion Kit
Before You Being
The installation and removal of modules that are part of the PowerFlex 750-Series Products, must be performed by personnel familiar with the
hardware topology of the product. Review product details that are in these manuals before servicing the product. A list of tasks and their related
publications are provided.
• How to use the service cart (PowerFlex 750-Series Service Cart and DCPC Module Lift, publication 750-IN105
)
• See PowerFlex 750-Series AC Drives Installation Instructions, publication 750-IN001
for information on:
• How to remove power from a PowerFlex 750-Series frame 8 or larger
• PowerFlex 750-Series AC input and DC bus voltage test points
• PowerFlex 750-Series lockout provisions
• PowerFlex 750-Series power module removal guidance
• Safety-related practices for electrical systems (NFPA 70E, Standard for Electrical Safety in the Work Place)
• Basic information to install, protect, wire, and ground pulse-width modulated (PWM) AC drives, (Wiring and Grounding for Pulse Width
Modulated (PWM) Drives, publication DRIVES-IN001
)
Required Tools
Aisle Clearance
The minimum aisle clearance that is required to maneuver and position the service cart is 914 mm (36 in.).
Ratcheting wrench 25 mm socket (used with electric drill) 13 mm socket
Torque wrench Ratcheting extension, 3 in. (76 mm) min T40 hexalobular bit
Electric drill with torque rating 11.3 N•m (100 lb•in), min Pliers T45 hexalobular bit