Rockwell Automation Publication 750-PM101B-EN-P - April 2022 111
Chapter 4 Troubleshooting
41 CurRegdOut
The output si
gnal of the current regulator used to
regulate the reactive current component which
includes the effect of both the proportional action
and the integral action.
REAL Volts
42 VqSyncRef
The final q-axis component of the voltage reference
that is connected to the modulator. This component
is used along with the d-axis component of the
voltage reference to generate the magnitude and
the angle of the final voltage reference connected to
the modulator.
REAL Volts
43 VdSyncRef
The final d-axis component of the voltage reference
that is connected to the modulator. This component
is used along with the q-axis component of the
voltage reference to generate the magnitude and
the angle of the final voltage reference connected to
the modulator.
REAL Volts
45 CurRegqI
The output of the integral term of the of the current
regulator used to regulate the active current
component.
REAL Volts
46 CurRegqP
The output of the proportional term of the of the
current regulator used to regulate the active current
component.
REAL Volts
47 VltRefLim
The limited value of the magnitude of the voltage
reference used to generate the three phase
modulator signals.
REAL Volts
Port 13 Testpoint Codes (Continued)
No. Display Name Description Data Type Units