Chapter Set-up Procedures: SMP PLUS
Controller without Options
3-6
3
Customer Settings (continued)
This mode is used for applications requiring across the line starting. The ramp time
is set for less than 1/4 second as shown in Figure 3.8.
Figure 3.8 - Full Voltage
100
Time (seconds)
Percent
Voltage
Full Voltage Start Selection without Options
Refer to Figure 3.9.
1. Starting Time – For full voltage starting, switches 7–9 must be OFF. This
results in a ramp period of less than 1/4 second
2. Kickstart Time – Set Kickstart Time rotary digital switch to OFF
3. Initial Torque – Set Initial Torque rotary digital switch to 9
4. Current Limit/Soft Start – For full voltage starting, switch 6 must be OFF
5. Energy Saver Select – Switch 5 must be OFF. Energy Saver is not available
6. Auxiliary Contact Select – Set switch 4 OFF if you want “normal” auxiliary
contacts, ON if you want “up-to-speed” auxiliary contacts.
7. Stall Select – Set switch 3 ON if you want the stall feature (or OFF if you do
not want this feature active)
NOTE: For resistive load operation, switch 3 must be OFF
Figure 3.9 - Set-up Procedure for Full Voltage (without Options)
Switch
TIME (seconds)
Number
1/4
9 Off
8 Off
7 Off
6 Off
5 ENERGY SAVER SELECT
4 AUXILIARY CONTACT SELECT
3 STALL SELECT
2 NOT USED
1 NOT USED
Initial Torque
Position 0 1 2 3 4 5 6 7 8 9
% of Locked Rotor Torque 5 10 20 30 40 50 60 70 80 90
Kickstart Time
Position 0 1 2 3 4 5 6 7 8 9
Time (Sec.) Off 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
Full Voltage
Starting
Full Voltage Start
Selection without
Options