EasyManuals Logo

Rockwell Automation Allen-Bradley SMC-PLUS Bulletin 150 User Manual

Rockwell Automation Allen-Bradley SMC-PLUS Bulletin 150
25 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
Chapter Troubleshooting
4-4
4
Figure 4.4 - Miscellaneous situations
Symptom Possible Causes Remedy
Motor current and
voltage fluctuates
with steady load
Check motor
Energy Saver
Verify the application of standard squirrel cage induction motor
Set Energy Saver Off (DIP switch #5 to Off) then restart If
problem stops, replace control module; If problems persists,
shut off ALL power to controller and check connections
Erratic operation
Loose connections Shut off ALL power to controller and check for loose
connections
Accelerates too fast
Incorrect starting time
Incorrect kickstart
Incorrect initial torque
Incorrect current limit setting
Increase starting time/Lower initial torque
Lower kickstart
Lower initial torque
Decrease current limit
Accelerates too slow
Incorrect starting time
Incorrect kickstart
Incorrect initial torque
Incorrect current limit setting
Decrease starting time
Increase kickstart time
Increase initial torque
Increase current limit
Fan doesn’t operate
(97A and 135A only)
Fan not wired properly Check fan wiring
Replace fan if necessary
Motor stops too
quickly with soft stop
option
Incorrect settings Verify that DIP switch settings are correct
Motor stopping time
is too slow with soft
stop option
Incorrect settings
Misapplication
Verify that DIP switch settings are correct
The soft stop option is intended for loads that stop suddenly
when voltage is removed from the motor
Motor surges still
occur with soft stop
option
Misapplication The soft stop option is intended for loads that stop suddenly
when voltage is removed from the motor
Refer to Publication 150-806 – Pump Control Option
Motor overheats
Duty Cycle Preset Slow Speed Option: Extended operation reduces motor
cooling efficiency. Consult motor manufacturer for limits of
operation
Smart Motor Brake Option: Check duty cycle
Accu-Stop Option: Extended operation at the preset slow
speed level reduces motor cooling efficiency. Consult motor
manufacturer for limits of operation. Verify maximum inertia
limits
When applying SMB, Accu-Stop, Preset Slow Speed and Slow Speed with braking, it may be necessary in some applications to consult with
motor manufacturer on motor heating due to the duty cycle, high load inertia or other application parameters.
Depending on the application, the SMB Smart Motor Braking, Accu-Stop, and Slow Speed with Braking options may cause some vibration or noise
during the stopping cycle and this may be minimized by lowering the braking current. If this is a concern in your application, consult the factory
prior to applying these options.
The control module is not intended for field repair. The entire module must be
replaced in the event of failure. The following procedure must be followed before
unplugging the control module.
WARNING: To avoid shock hazard, disconnect main power before
working on the controller, motor, or control devices such as Start/Stop
push buttons.
!
CAUTION: Make sure that wires are properly marked and DIP switch
settings are recorded.
!
Control Module
Removal

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley SMC-PLUS Bulletin 150 and is the answer not in the manual?

Rockwell Automation Allen-Bradley SMC-PLUS Bulletin 150 Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley SMC-PLUS Bulletin 150
CategoryController
LanguageEnglish

Related product manuals