Rockwell Automation Publication 520-UM001I-EN-E - July 2016 103
Programming and Parameters Chapter 3
Communications Group (continued)
C133 [EN Subnet Cfg 1] Related Parameter(s): C128
C134 [EN Subnet Cfg 2]
C135 [EN Subnet Cfg 3]
C136 [EN Subnet Cfg 4]
PowerFlex 525 only.
Sets the bytes of the subnet mask. A reset or power cycle is required after selection is made.
Values Default: 0
Min/Max: 0/255
Display: 1
PF 525
255.255.255.0
[EN Subnet Cfg 1]
[EN Subnet Cfg 2]
[EN Subnet Cfg 3]
[EN Subnet Cfg 4]
IMPORTANT
C128 [EN Addr Sel] must be set to 1 “Parameters.
C137 [EN Gateway Cfg 1] Related Parameter(s): C128
C138 [EN Gateway Cfg 2]
C139 [EN Gateway Cfg 3]
C140 [EN Gateway Cfg 4]
PowerFlex 525 only.
Sets the bytes of the gateway address. A reset or power cycle is required after selection is made.
Values Default: 0
Min/Max: 0/255
Display: 1
PF 525
192.168.1.1
[EN Gateway Cfg 1]
[EN Gateway Cfg 2]
[EN Gateway Cfg 3]
[EN Gateway Cfg 4]
IMPORTANT
C128 [EN Addr Sel] must be set to 1 “Parameters.
C141 [EN Rate Cfg]
PowerFlex 525 only.
Sets the network data rate at which EtherNet/IP communicates. A reset or power cycle is required after selection is made.
Options 0 Auto detect” (Default)
1 “10Mbps Full”
2 “10Mbps Half
3 “100Mbps Full”
4 “100Mbps Half