EasyManua.ls Logo

Rockwell Automation B Series

Rockwell Automation B Series
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 520-UM001I-EN-E - July 2016 233
PID Set Up Appendix F
2. Adjust the integral gain (leave the proportional gain set as in Step 1). After
a step change in the PID Feedback:
If the response is too slow (see Slow Response – Over Damped
on
page 233), or the PID Feedback does not become equal to the PID
Reference, decrease A462 or A474 [PID x Integ Time].
If there is a lot of oscillation in the PID Feedback before settling out
(see Oscillation – Under Damped
on page 233), increase A462 or
A474 [PID x Integ Time].
3. At this point, the differential gain may not be needed. However, if after
determining the values for A461 or A473 [PID x Prop Gain] and A462 or
A474 [PID x Integ Time]:
Response is still slow after a step change, increase A463 or A475 [PID x
Diff Rate].
Response is still unstable, decrease A463 or A475 [PID x Diff Rate].
The following figures show some typical responses of the PID loop at different
points during adjustment of the PID Gains.
Unstable Response
Slow Response – Over Damped
Oscillation – Under Damped
PID Feedback
PID Reference
Time
PID Feedback
PID Reference
Time
PID Feedback
PID Reference
Time

Table of Contents

Related product manuals