296 Rockwell Automation Publication 750-TG100B-EN-P - June 2019
Chapter 11 Start Up After Repairs
3. For drives and bus supplies, measure the 240V AC control voltage at the
appropriate terminals:
For frame 7 drives and bus supplies, measure terminals L and N on
terminal block TB3.
For frames 8…15 drives and bus supplies, in the input bay, measure
terminals L and N on terminal block TB2.
Frame 10 Input Bay Shown