Input and Output Connections
AC-425 Hardware Installation and User Manual 21
Figure 10: Normally Open Input Connection
4.1.2 Normally Closed Input Connection
A Normally Closed Input has two states:
Switch ClosedNormal State:
Loop resistance = 0 (short circuit)
Switch Open Abnormal State:
Loop resistance = Infinite (open circuit)
Figure 11: Normally Closed Input Connection
4.1.3 Normally Open Supervised Single EOL Resistor Input
Connection
Connect an 8.2 k resistor in parallel to the input switch contacts.
A Normally Open Supervised Input has 3 states:
Switch OpenNormal State:
Loop resistance = 8.2 k
Switch Closed Abnormal State:
Loop resistance = 0 (short circuit)