3 Phase Power Analyser / EN
09/30/16 Version No. 00 4
III. SPECIFICATIONS
3-1 Environmental Conditions
• Altitude up to 2000 metres
• Indoor use only
• Ambient operating temperature: 0 to 40°C
• Operating humidity : Max 80%RH ≤ 31°C decrease linearly to 50% relative humidity at 40°C
(non-condensing).
• Storage temperature and humidity : -10 to 60°C R.H. < 70% non-condensing.
3-2 Safety Specifications
IPM 3600N Power Analyser
Category Rating : CAT III 1000V per IEC 61010-1
Pollution Degree 2
: IEC 61010-1 2nd Edition
ICA 3600N AC current probes:
Current Clamps, model ICA 3600N, to be used only with the Three-Phase power analyzer,
model IPM 3600N.
Category Rating: CAT III 600V per IEC61010-1,
Pollution Degree2.
: IEC 61010-1 2nd Edition and IEC61010-2-032
Input : AC 1000A maximum.
Output : 0.35mV/A
Voltage test leads:
Category Rating : CAT III, 1000V, AC 10A Max.
Alligator clip:
Category Rating : CAT III, 1000V, AC 10A Max.
Category definitions
Measurement
Category
Application
I
Measurements on circuits not directly connected to mains.
Examples include: Measurements on battery powered equipment and
specially protected (internal) mains-derived circuits.
II
Measurements on circuits directly connected to the low voltage installation.
Examples include: Household appliances, portable tools and similar equipment.
III
Measurements performed in the building installation.
Examples include measurements on distribution boards, junction boxes,
socket-outlets and wiring and cables in the fixed installation.
IV
Measurements performed at the source of the low-voltage installation.
Examples include measurements on primary over current protection devices
and electricity meters