EMI and Environmental Tests 33
Test Description Test Levels Severity Levels
Signal Ports
5 kV (Fail-Safe
Relay Output)
D.C. Power Ports
H.V. Impulse
A.C. Power Ports
5 kV
Signal Ports
5 kV (Fail-Safe
Relay Output)
D.C. Power Ports 5 kV
Dialiectric Strength
A.C. Power Ports 5 kV
Signal Ports 2 kVAC
D.C. Power Ports 1.5 kVDC
IEC 1613/C37.90
H.V. Impulse
A.C. Power Ports 2 kVAC
Signal Ports
2.5 kV common
mode @1 MHz
D.C. Power Ports
Oscillatory
A.C. Power Ports
2.5 kV common, 1 kV
diff. mode@1 MHz
Signal Ports +/- 4 kV @ 2.5 kHz
D.C. Power Ports
A.C. Power Ports
IEC 1613/C37.90.1
Fast Transient
Earth Ground Ports
+/- 4 kV
IEC 1613/C37.90.2 Radiated RFI Enclosure Ports 35 V/m
Enclosure Contact +/- 8 kV
IEC 1613/C37.90.3 ESD
Enclosure Air +/- 15 kV
NOTE
In the case of an all fiber port configuration, this product meets all Class 2 requirements. Otherwise,
all Class 1 requirements are met for copper ports.
If the unit contains copper ports, the IEC 1613 conformance is Class 1, during which disturbance
errors may occur but recovery is automatic.
If the unit contains all fiber ports, the IEC1613 conformance is Class 2, during which no disturbance
errors will occur.
Table 11: Environmental Type Tests
Test Description Test Levels
IEC 60068-2-1 Cold Temperature Test Ad -40 °C (-40 °F), 16 Hours
IEC 60068-2-2 Dry Heat Test Bd 85 °C (185 °F), 16 Hours
IEC 60068-2-30 Humidity (Damp Heat, Cyclic) Test Db
95% (non-condensing),
55 °C (131 °F), 6 cycles
IEC 60068-21-1 Vibration 2g @ 10 - 150 Hz
IEC 60068-21-2 Shock 30g @ 11 mS