RUGGEDCOM RSG2488
Installation Guide
Chapter 6
Certification
EMI and Environmental Tests 33
Test Description Test Levels Severity Levels
Signal Ports
5 kV (Fail-Safe
Relay Output)
D.C. Power Ports
H.V. Impulse
A.C. Power Ports
5 kV
Signal Ports
5 kV (Fail-Safe
Relay Output)
D.C. Power Ports 5 kV
Dialiectric Strength
A.C. Power Ports 5 kV
Signal Ports 2 kVAC
D.C. Power Ports 1.5 kVDC
IEC 1613/C37.90
H.V. Impulse
A.C. Power Ports 2 kVAC
Signal Ports
2.5 kV common
mode @1 MHz
D.C. Power Ports
Oscillatory
A.C. Power Ports
2.5 kV common, 1 kV
diff. mode@1 MHz
Signal Ports +/- 4 kV @ 2.5 kHz
D.C. Power Ports
A.C. Power Ports
IEC 1613/C37.90.1
Fast Transient
Earth Ground Ports
+/- 4 kV
IEC 1613/C37.90.2 Radiated RFI Enclosure Ports 35 V/m
Enclosure Contact +/- 8 kV
IEC 1613/C37.90.3 ESD
Enclosure Air +/- 15 kV
NOTE
• In the case of an all fiber port configuration, this product meets all Class 2 requirements. Otherwise,
all Class 1 requirements are met for copper ports.
• If the unit contains copper ports, the IEC 1613 conformance is Class 1, during which disturbance
errors may occur but recovery is automatic.
• If the unit contains all fiber ports, the IEC1613 conformance is Class 2, during which no disturbance
errors will occur.
Table 11: Environmental Type Tests
Test Description Test Levels
IEC 60068-2-1 Cold Temperature Test Ad -40 °C (-40 °F), 16 Hours
IEC 60068-2-2 Dry Heat Test Bd 85 °C (185 °F), 16 Hours
IEC 60068-2-30 Humidity (Damp Heat, Cyclic) Test Db
95% (non-condensing),
55 °C (131 °F), 6 cycles
IEC 60068-21-1 Vibration 2g @ 10 - 150 Hz
IEC 60068-21-2 Shock 30g @ 11 mS