Chapter 6
Certification
RUGGEDCOM RSG2488
Installation Guide
32 EMI and Environmental Tests
Section 6.3
EMI and Environmental Tests
The RSG2488 has passed the following EMI and environmental tests.
Table 10: IEC 61850-3 EMI Type Tests
Test Description Test Levels Severity Levels
Enclosure Contact +/- 8 kV
IEC 61000-4-2 ESD
Enclosuer Air +/- 15 kV
4
IEC 61000-4-3 Radiated RFI Enclosure Ports 20 Vm X
Signal Ports +/- 4 kV @ 2.5 kHz X
D.C. Power Ports
A.C. Power Ports
IEC 61000-4-4 Burst (Fast Transient)
Earth Ground Ports
+/- 4 kV 4
Signal Ports
D.C. Power Ports
A.C. Power Ports
IEC 61000-4-6 Induced (Conducted) RFI
Earth Ground Ports
10 V 3
IEC 61000-4-8 Magnetic Field Enclosure Ports
40 A/m, continuous,
1000 A/m for 1 s
D.C. Power Ports
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
IEC 61000-4-29
Voltage Dips and
Interrupts (D C.
Power Ports)
A.C. Power Ports
30% for 1 period
60% for 50 periods
IEC 61000-4-11
Voltage Dips and
Interrupts (A. C.
Power Ports)
A.C. Power Ports
100% for 5 periods
100% for 50 periods
Signal Ports
D.C. Power PortsIEC 61000-4-12 Damped Oscillatory
A.C. Power Ports
2.5kV common, 1kV
diff. mode@1MHz
3
Signal Ports
IEC 61000-4-16 Mains Frequency Voltage
D.C. Power Ports
30 V Continuous,
300 V for 1s
4
IEC 61000-4-17
Ripple on D.C.
Power Supply
D.C. Power Ports 10% 3
Signal Ports
2 kVAC (Fail-
Safe Relay Output)
D.C. Power Ports 1.5 kVDC
IEC 60255-5
Dialiectric Strength
A.C. Power Ports 2 kVAC

Other manuals for RuggedCom RSG2488