6.2 Commissioning
If your system is an back-up or off-grid system, make sure your configuration can cover the worst
situation to avoid battery to be over-discharged.
Step 1
Turn on the breaker in battery, then turn on the inverter/charger isolator.
Step 2
Hold down the switch button of the battery for 3s to start the battery.
Step 3
Set the corresponding inverter brand on the battery display.
Step 4
Finish the setting on inverter/charger or any other control devices, if everything is correct,
you are ready to use
6.3 Switch off battery
Step 1
Turn off the inverter.
Step 2
Hold down the switch button on the battery for 3s to turn off the battery.
Step 3
Turn off the breaker in battery.
6.4. Troubleshooting
Items
Solution
Measure
Unable to start
1. Switch on battery and press RESET 6s to observe
whether the battery can be started.
2. Charge the battery use a charge or inverter to provide
54~57.6V voltage and observe it can be started.
If the abnormal status
still alive after above
steps, please contact
your supplier.
Unable to charge
1. Check whether the cable connection between the
battery and the inverter/charger is correct.
2. Check whether the inverter/charger setting is correct.
3. Check whether the battery is in charge protection
mode, if yes, try to discharge the battery.