VG5 Installation & Quick-Start Manual 97
H1-04
Terminal 6
Selection
(Terminal 6 Sel)
00~77 1
4 (3)
(Note
15)
x B B B B
H1-05
Terminal 7
Selection
(Terminal 7 Sel)
00~77 1
6 (4)
(Note
15)
x B B B B
H1-06
Terminal 8
Selection
(Terminal 8 Sel)
00~77 1
8 (6)
(Note
15)
x B B B B
Note 15: Factory settings in the parentheses are values obtained at 3-wire initialization.
Terminal
Function H2 Digital Outputs
H2-01
Multi-function Input
Terminal
9-10
(Terminal 9 Sel)
00~37 1 0
Multi-function output 1 (terminal
9, terminal 10)
(same as F5-01)
x B B B B
H2-02
Multi-function Input
Terminal 25
(Terminal 25 Sel)
00~37 1 1
Multi-function output 2 (terminal
25, terminal 27)
(same as F5-01)
x B B B B
H2-03
Multi-function Input
Terminal 26
(Terminal 26 Sel)
00~37 1 2
Multi-function output 3 (terminal
26, terminal 27)
(same as F5-01)
x B B B B
Function H3 Analog Inputs
H3-01
Signal Level Selec-
tion Terminal 13
(Term 13 Signal)
0, 1 1 0
0: (0 - 10 VDC)
1: (–10 +10 VDC)
x B B B B
H3-02
(Terminal 13 Gain)
0.0~
1000.0
0.1% 100.0
Frequency reference gain of AI-
14U, AI-14B (3ch addition
input), DI-08, and DI-16 is com-
mon.
o B B B B
H3-03
(Terminal 13 Bias)
–100.0
~
+100.0
0.1% 0.0
Frequency reference gain of AI-
14U, AI-14B (3ch addition
input), DI-08, and DI-16 is com-
mon.
o B B B B
H3-04
Terminal 16 Signal
Level Selection
(Term 16 Signal)
0, 1 1 0
0: (0 - 10 VDC)
1: (–10 +10 VDC)
x B B B B
H3-05
Terminal 16 Multi-
function Analog
Input
(Terminal 16 Sel)
0~1F 1 0
Multi-function analog input selec-
tion (terminal 16)
0: Auxiliary Reference
1: Frequency Gain
2: Frequency Bias
4: Voltage Bias
5: Accel/Decel Change
6: DC Brake Current
7: Overtorque Level
8: Stall Prevention Level
9: Reference Lower Limit
A: Jump Frequency
B: PID Feedback
C: PID Setpoint
D: Frequency Bias 2
10: Forward Torque Limit
11: Reverse Torque Limit
12: Regenerative Torque Limit
13: Torque reference
14: Torque Compensation
15: Forward/Reverse Torque Limit
1F: Not Used
x B B B B
Function
Parameter
No.
Name
(Digital Operator
Display)
Setting
Range
Setting
Unit
Factory
Setting
Remarks
(Digital Operator Display)
Change
during
Operation
o: Enabled
x: Disabled
Parameter Access Level
User
Setting
V/f
V/f
w/
PG
Open
Loop
Vector
Flux
Vector
Appendix
VG5 Parameters