For any advanced settings please access the Installer Mode. Here you will have the possibility to adjust your
frost setpoint, to set the temperature offset and also to choose from two temperature increments. Please follow
the steps below in order to modify the installer parameters.
dxx Function Parameter Description Default
value
d01
Temperature display
increments
0.1 or 0.5°C
Select temperature display
increments
0.5°C
d02 Temperature oset +/-3.0°C
Calibrate your thermostat
temperature
0.0°C
d03 Frost setpoint 5.0-17.0°C Set the Frost Point temperature 5.0°C
RESET
+Hr
SELECT SET
RESET
+Hr
SELECT SET
3 Sec 3 Sec
3 Sec
RESET
+Hr
SELECT SET
Press and hold all three
buttons together for 3 sec.
Press Set in order to
changed the setting.
RESET
+Hr
SELECT SET
0. 5
°C
Press Up/Down to select
the desired value.
1 2
3 4
Installer Mode
10 RT510RF Installation Manual

Other manuals for Salus RT510RF

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Salus RT510RF and is the answer not in the manual?

Salus RT510RF Specifications

General IconGeneral
Power Supply2 x AA batteries
Frequency868 MHz
Temperature Range5°C to 35°C
DisplayLCD
Programming7-day programmable
Temperature Control Accuracy±0.5°C
Hysteresis±0.5°C
Control AlgorithmTPI
Operating ModesManual, Holiday
CompatibilityCombi Boilers
Programmable Periods6 periods per day

Related product manuals