EasyManua.ls Logo

Samson 3731-3 - Technical Data

Samson 3731-3
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.3 Technical data
EB 8387-3 EN 11
Design and principle of operation
Type 3731-3 Ex d Positioner (technical data in test certificates additionally apply for explosion-protected devices)
Rated travel Adjustable Direct attachment to Type 3277: 3.6 to 30 mm
Attachment acc. to IEC 60534-6 (NAMUR): 3.6 to 300 mm
Attachment to rotary actuators (VDI/VDE 3845): 24° to 100°
Travel range Adjustable Adjustable within the initialized travel/angle of rotation;
travel can be restricted to
1
5
at the maximum
Reference variable w Signal range 4 to 20 mA, 2-wire unit, reverse polarity protection,
min. span 4 mA, static destruction limit 40 V, internal current limit 60 mA
Shutdown action Type 3731-3xxxxxx0
00x1x00: Emergency shutdown at 0 mA
Type 3731-3xxxxxx1
00x1x00: Emergency shutdown at 3.85 mA ± 0.05 mA
Minimum current 3.6 mA for display
Voltage compliance
9 V corresponds to 450
at 20 mA
Communication
Local communication SAMSON SSP interface and serial interface adapter
Software requirements TROVIS-VIEW with device-specific module for Type 3731-3
HART
®
communication HART
®
field communication protocol
Impedance in HART
®
frequency range: Receiving approx. 455
, sending 185
Software requirements For handheld communicator: device description for Type 3731-3
For PC: DTM file acc. to Specification 1.2, suitable for integrating the positioner in
frame applications that supports the FDT/DTM concept (e.g. PACTware);
integration into AMS™ Suite available.
Supply air Pressure Type 3731-321, Type 3731-327: 1.4 to 7 bar (20 to 105 psi)
Type 3731-323: 1.4 to 6 bar (20 to 90 psi)
Air quality acc. to
ISO 8573-1
edition 2004
Max. particle size and density: Class 4 · Oil content: Class 3
Moisture and water: Class 3
Pressure dew point: At least 10 K beneath the lowest ambient temperature to be
expected
Signal pressure (output) 0 bar up to supply pressure · Limitable to 1.4/2.4/3.7 ±0.2 bar via software
Characteristic Linear/equal percentage/reverse equal percentage
Butterfly valve/Rotary plug valve/Segmented ball valve: linear/equal percentage
User-defined (over operating software and communication)
Deviation from terminal-based conformity
1 %
Hysteresis
0.3 %
Sensitivity
0.1%
Transit time Separately adjustable up to 240 seconds for supply air and exhaust air
Direction of action Reversible
Air consumption, steady-state Independent from supply pressure < 110 l
n
/h

Table of Contents