11 Code list
Code
no.
Parameter – Display, values
[default setting]
Description
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
0
Operating mode
[MAN]
AUtO · SAFE
ESC
AUtO Automatic mode
MAN Manual mode
SAFE Fail-safe position
ESC Escape
In MAN and AUtO mode, the system deviation is represented by
bar elements on the display.
If the positioner has been initialized, the numerical reading indi
-
cates the valve position or the angle of rotation in %, otherwise
the position of the lever in relation to the central axis is displayed
in degrees °.
Switchover from automatic to manual mode is smooth.
In fail-safe position, the S icon appears on the display.
Init · AtO · AtC Init Start initialization
Allocate closed position:
AtO: AIR TO OPEN (valve CLOSED in fail-safe position) or
AtC: AIR TO CLOSE (valve OPEN in fail-safe position)
1
Manual reference variable
w
[0] to 100 %
of the nominal range
Setting the manual reference variable w
The current travel/angle is displayed in % when the positioner
has been initialized, otherwise the position of the lever in relation
to the central axis is indicated in degrees °.
Can only be selected when Code 0 = MAN.
2
Reading direction
[Normal] or upside down
ESC
The reading direction of the display is turned by 180°.
3
Enable configuration
[No]
YES
ESC
Enables the option to modify data (automatically deactivated
when the rotary pushbutton has not been operated for 120 s.)
HART blinks on the display when the on-site operation is locked
over HART
®
communication.
Codes marked with an asterisk (*) can only be read and not
overwritten.
Codes can also only be read over the SSP interface.
EB 8387-3 EN 65
Code list