EasyManua.ls Logo

Samson 3731-3 - Operation; Enabling Parameters and Configuration

Samson 3731-3
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Operation
WARNING!
The actuator stem moves while the positioner
is being operated.
Do not touch the actuator stem or obstruct it
to avoid risk of injury to hands or fingers.
8.1 Enabling and selecting
parameters
All codes with their meanings and default
settings are listed in the code list in sec
-
tion 11 on page 65 onwards.
The codes which are marked with an aster-
isk (*) must be enabled with Code 3 before
the associated parameters can be config-
ured as described below.
Code 3
Configuration
not enabled
Configuration
enabled
Turn
Code 3, display: No
Press , Code 3 blinks.
Change the setting of Code 3.
Turn
YES
Turn , display:
The configuration is enabled.
You can now configure codes one after the
other:
Turn and select the required code.
Press to access the selected code. The
code number starts to blink.
Turn and select the setting.
Press to confirm the selected setting.
Note: If no settings are entered within 120
seconds, the enabled configuration function
becomes invalid and the display changes to
Code 0.
Canceling the setting
Canceling the setting
To cancel a value before it is confirmed (by
pressing the rotary pushbutton ) without
the value you have just selected being
adopted:
Turn
ESC
Press to confirm the cancelation.
The entry is ended without the value you
have just selected being adopted.
60 EB 8387-3 EN
Operation

Table of Contents

Related product manuals