NOTICE
If the positioner is mounted onto another ac
-
tuator or its mounting position is changed,
reset the positioner to its default settings be
-
fore re-initializing it. Refer to section 7.7.
During initialization the positioner adapts it
-
self optimally to the friction conditions and
the signal pressure requirements of the con
-
trol valve.
The type and extent of self-adaptation de
-
pends on the initialization mode selected:
4
MAX maximum range (standard range)
Initialization mode for simple start-up of
valves with two clearly defined mechani-
cal end positions, e.g. three-way valves
(see section 7.5.1)
4
NOM nominal range
Initialization mode for all globe valves
(see section 7.5.2)
4
MAN manually selected range
Initialization mode for globe valves with
an unknown nominal range (see section
7.5.3)
4
SUB substitute calibration (emergency
mode)
This mode allows a positioner to be re
-
placed while the plant is running, with
the least amount of disruption to the
plant (see section 7.5.4)
Note: The initialization procedure can be in
-
terrupted while running by pressing the ro
-
tary pushbutton ( ). StOP appears three
seconds long and the positioner then
changes to the fail-safe position (SAFE). The
fail-safe position can be canceled again
over Code 0 (see section 8.2.2).
Alternating displays:
Initialization running
Initialization progress
indicated
(MAX, NOM, MAN or SUB
appears, depending on the
initialization mode selected)
Initialization successful
Positioner in automatic
mode
The time required for an initialization pro
-
cess depends on the stroking speed of the
actuator and may take several minutes.
After a successful initialization, the
positioner runs in automatic mode indicated
by the closed-loop control icon.
A malfunctioning leads to the process being
interrupted. The initialization error appears
on the display according to how it has been
classified by the condensed state. See sec-
tion 8.3 on page 60).
Note: The setting of Code 48 - h0 = YES
starts the plotting of the reference graphs re
-
quired for valve diagnostics (drive signal
steady-state d1 and hysteresis d2) after ini
-
tialization. tESt and d1 and d2 appear on
the display in an alternating sequence.
An unsuccessful plotting of the reference
graphs is indicated on the display by Code
48 - h1 and Code 81 (see error code list).
The positioner still works properly, even
though the reference graph plotting has not
been completed successfully.