EB 8355-1 EN 37
Connections
The wires for the reference variable must be
connected to the terminals 11 and 12 locat-
ed in the housing.
In general, it is not necessary to connect the
positioner to a bonding conductor. Should
this be required, however, this conductor can
be connected inside the device or outside on
the device.
Depending on the version, the positioner is
equipped with inductive limit switches and/
or a solenoid valve.
Versions with position transmitter do not per-
mit the connection of additional equipment.
The position transmitter is operated on a
two-wire circuit. The usual supply voltage is
24VDC.
Taking the resistance of the supply leads into
account, the voltage at the position transmit-
ter terminals can be between 12 and
45VDC.
RefertoFig.11ortothelabelonthetermi-
nal block.
Accessories:
CableglandM20x1.5:
Version Order no. Clamping
range
Black plastic 1400-6985 5.5to13mm
Blue plastic 1400-6986 5.5to13mm
Nickel-plated brass 1890-4875 6to12mm
AdapterM20x1.5to½NPT:
Powder-coated aluminum,
order no. 0310-2149
4.2.1 Switching amplier
The operation of the inductive limit contacts
requiresswitchingampliersinaccordance
withEN60947-5-6tobeconnectedinthe
output circuit. Observe the relevant regula-
tions for installation in hazardous areas.
+41 –42 +51 –52 +81 –82 +31 –32
G
E
i
+
–
(B)
A
(A)
B
A
+11 –12 +11 –12
E
i
/
E
i
/
AA
mA control
signal
6to24VDC
solenoid valve
Transmitter supply voltage
for position transmitter only
Rear Version with position transmitter
Switchingamplier
acc.toEN60947-5-6
Fig.11: Electrical connections