EasyManua.ls Logo

Samson 3766 - Upgrading the Positioner

Samson 3766
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EB 8355-1 EN 47
Upgrading the positioner
6 Upgrading the positioner
Thepneumaticpositioner(3766-x...x.04
and higher) can be converted to form a
Type3767ElectropneumaticPositioner.
Upgrade of explosion-protected versions on-
ly on request.
BesidestheType6112i/pModule(see-
Table11),theassociatedconversionkit(in-
cluding cable gland, fastening screw, clamps
and cables) must be ordered.
1. Remove the holder with the terminal
block (if used).
2. Unscrew the connecting plate (3) and re-
move the silicone hose (2).
Remove the guard plate (4) and pneu-
maticscrewtting(1).
3. Connect the connecting cable to the ter-
minalblockandthei/pmodule(6).Lead
the blue cable to the minus side and the
red cable to the plus side. Fasten the ca-
bles with terminal screws.
4. Checkwhethertheseals(7,8)areprop-
erly inserted on the bottom section of the
i/p module. When the module is in-
stalled(brokenlineinFig.16),theseal
includingrestrictionandltermustbelo-
cated on the right above the inner hole
(supply).
5. Fasten the i/p module and terminal block
holder each with two screws.
6. Seal the housing on the side using the
cablegland(5)orastopperwithseal.
7. Change model index on the nameplate
toType3767i/pPositioner.
For details on Type3767 Positioners, refer to
Mounting and Operating Instructions
uEB8355-2.
1234
5678
Fig.15: Upgrading the positioner