EB 8355-1 EN 41
Operation
4. Turnthezeroadjuster(6.2)againuntil
the pressure gauge indicates the required
signal pressure (see section 4.1.2).
5. If no pressure gauge has been installed,
setthestartingpointto0.97barinstead.
After attaching and tuning of the positioner,
make sure that the vent plug of the housing
cover faces downward when the valve is in-
stalled.
5.2 Changing the operating di-
rection
If the operating direction of directly attached
positioners(Fig.2)istobechangedafter
they have been installed, turn the turnboard
(7)andchangethepositionoftheconnec-
tion block, positioner and clamp (1.2).
ForattachmentaccordingtoIEC60534-6
(NAMUR),turntheturnboard(7)andthe
positionerontheadapterhousing(Fig.5).
In positioners for rotary actuators, reassign
thecamdiskasshowninFig.8andFig.9.
Fordetailsonchangingtheturnboard(7)re-
fer to section 3.
NOTICE
!