EasyManua.ls Logo

Samson 3766 - Page 45

Samson 3766
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EB 8355-1 EN 45
Operation
Zero point adjustment
1. Use the input signal of the positioner to
move the valve to closed position (valve
CLOSED,travel0%).
2. The ammeter must now indicate approx.
4mA.
3. Correct smaller deviations at the ZERO
potentiometer until the meter shows ex-
actly4mA.
For larger deviations that cannot be cor-
rected using the potentiometer (adjust-
ment range of approx. 20 turns), set the
switches 1 and 2 to indicate an mA val-
ue which is within the adjustment range
of the ZERO potentiometer.
4. Setthezeropointtoexactly4mAusing
the ZERO potentiometer.
Adjusting the span
1. Use the input signal of the positioner to
move the valve to closed position (valve
CLOSED,travel100%).
2. The ammeter must now indicate approx.
20mA.
3. Correct smaller deviations at the SPAN
potentiometer until the meter shows ex-
actly20mA.Ifdeviationsaretoohigh,
set the switches 3 and 4 to indicate an
mA signal which is within the adjustment
range of the SPAN potentiometer.
4. Turn the SPAN potentiometer until the
ammetershowsexactly20mA.
Since the zero point and span have a
mutualinuenceoneachother,repeat
the correction procedure at both potenti-
ometers until both values are correct
.

Related product manuals