14 EB 8546 EN
Mounting the supply pressure regulator
Type4708-55xxforTypes3725,4763,
and 4765 Positioners
1. Screw the special nuts (5) into the connect-
ing holes of the positioner.
2. Insert the gasket (2) into the recess of the
adapter plate (1).
3. Slide the special hollow screws (6) for
SUPPLY and (7) for OUTPUT into the con-
necting holes of adapter plate (1).
4. Place the supply pressure regulator onto
the positioner and fasten it using the two
special screws.
5. Seal the spare connections with stoppers
(4) to prevent dirt from entering the de
-
vice.
Type4708-64xxforType3277Actuator
Before mounting, check whether the tip of
the gasket (1.2) projecting from the side of
the connection block (1) is positioned to
match the actuator symbol (1.3) for the actu-
ator's fail-safe action "actuator stem ex-
tends" or "actuator stem retracts". If this is
not the case, proceed as follows:
1. Unscrew the three Phillips screws (3.1),
lift off the cover (1.1). Turn the gasket
(1.2) by 180° and re-insert it. Continue
with reassembly.
2. Place the connection block (1) with the
inserted O-ring against the positioner
and actuator yoke and fasten using the
hexagonal socket screw (3).
3. Place the supply pressure regulator with
O-ring on the connection block and fas-
ten it with hexagonal socket screw (2).
6
0
SAMSON 4763
4708-552.
6
0
1