22 EB 8359-2 EN
Mounting and start-up
5 Mounting and start-up
To attach the positioner to valves with cast
yokes according to IEC60534-6 (NAMUR
rib), mounting parts (order no. 1400-5745)
are used. For valves with rod-type yokes, the
mounting kit (order no. 1400-5745) and
additionally the mounting kit (order no.
1400-5342) are necessary (see also
accessories in section3.1 on page16).
Since the positioner can be attached on ei-
ther side of the valve, the physical location
(left or right attachment) should be deter-
mined before actual attachment.
Î See Fig.6 to Fig.9 on page27.
5.1 Attachment to valve with
cast yoke
3. Fasten the plate (20) to the stem connec-
tor (22) of the valve using the screws
(21).
4. Unscrew the positioner cover and secure
the positioner to the valve yoke using the
fastening screw (15). The O-ring includ-
ed in the mounting kit is not required for
this positioner. Make sure that the pin (2)
is inserted through the wire strap and, as
a result, clamped against the plate (20).
5.2 Attachment to valve with
rod-type yoke
1. Fasten the plate (20), off-centered, to the
travel indicator (24) of the plug stem (23)
using the screws (21).
2. Place both the support (28) and the
clamping plate (26) on the rod (27) and
lightly fasten. Move the support until both
the center of the plate (20) and the sup-
port (28) are aligned when the valve is
at half of the valve travel.
3. Fasten tight the support and the clamp-
ing plate.
4. Mount the positioner to the support using
the fastening screw (15). Make sure that
the pin (2) is inserted through the wire
strap and, as a result, clamped against
the plate (20).
5.3 Housing cover
After attaching the positioner, make sure that
the vent plug of the housing cover faces
downward when the valve is installed.
Legend for Fig.3 and Fig.4:
1 Lever
2 Pin
2.1 Nut
15 Fastening screw
20 Plate
21 Screw
22 Stem connector
23 Plug stem
24 Travel indicator
26 Clamping plate
27 Rod (pillar)
28 Support