EasyManua.ls Logo

Samson 4763 - Positioner Adjustment and Calibration

Samson 4763
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28 EB 8359-2 EN
Operating the positioner
6.1.1 Determining and
changing the operating
direction
For an increasing input signal (reference
variable), the signal pressure p
st
can either
be increasing (direct action <<) or decreas-
ing (reverse action <>).
Similarly, as the reference variable decreas-
es, the signal pressure can either decrease
(direct action <<) or increase (reverse action
<>).
On the apper plate, the operating direction
is indicated by symbols (direct <<, reverse
<>). Depending on the position of the ap-
per plate, the adjusted operating direction
and the associated symbol become visible.
If the required operating direction does not
correspond to the visible symbol or if the op-
erating direction is to be changed, proceed
as follows:
1. Unscrew both screws on the cover plate
and lift off the nozzle block along with
the cover plate.
2. Reinstall the nozzle block turned 180°
together with the cover plate and
refasten.
Make sure that the nozzle block and apper
plate are correctly located above or below
the feeler pin as shown in Fig.10.
If the operating direction is to be changed
after the initially determined arrangement of
positioner and actuator, note that the
positioner must be mounted in a different
location and the nozzle block must be
turned.
Make sure the location of the lever (1) and
the plate (20), "lever on top of plate" or
reversed "plate on top of lever" is correct
(Fig.6 to Fig.9).

Other manuals for Samson 4763