34 EB 8359-2 EN
Converting the electropneumatic into a pneumatic positioner
7 Converting the
electropneumatic into a
pneumatic positioner
The electropneumatic positioner can be con-
verted into a Type4765 Pneumatic Position-
er with a conversion kit.
Î Required conversion kits: see Table 2
1. Unscrew fastening screws and lift the i/p
converter together with the printed circuit
board out of the positioner housing.
2. Unthread cable gland (1). Plug on hose
(5) and screw the connecting nipple (4)
of the conversion kit tightly on the hous-
ing.
3. Insert sealing element (7) into connecting
plate (6) and fasten it tight into the hous-
ing.
4. Push the free end of the hose onto the
connecting plate (6).
For details on the converted Type4765
Positioner refer to Mounting and Operating
Instructions u EB8359-1.