5-2 EB2111/2121/2123 EN
Installation
Support or suspension
The plant engineering company is responsi-
ble for selecting and implementing a suitable
support or suspension of the installed regula-
tor and the pipeline.
Depending on the regulator version and
mounting position, the valve, actuator and
control thermostat must be supported or sus-
pended.
Do not attach supports directly to the valve
or control thermostat.
Temperature sensor
Galvanic corrosion due to incorrectly
selected materials of the mounting parts.
On installing the sensor or thermowell, only
combine the same kind of materials (e.g.
stainless steel with stainless steel or copper
together with other copper materials).
The temperature sensor, even together with a
thermowell, can be installed in any position
as required. However, make sure its entire
length is immersed in the process medium to
be controlled. It must be installed in a loca-
tion where overheating or considerable
idling times cannot occur.
Note
NOTICE
!
NOTICE
!
Suspended mounting
position
− All versions
Upright mounting
position
Not permissible
Any mounting position
Not permissible
Fig.5-1: Mounting position of Type1 and
Type4
Suspended mounting
position
− All versions
Upright mounting
position
− DN15to80only
Any mounting position
Not permissible
Fig.5-2: Mounting position of Type4u