3-66 Samsung Electronics
TANK-RECEIVER
SVC CODE
Weight
information
Fig
DB96-21951A 4.97kg
3) Checking of oil circulating system
Oil separator capillary tube or lter of block 
- If lter or capillary tube of oil separator lower column is blocked by alien substance etc.., can become cause of compressor break-
down because oil is not collected.
- Can doubt that is blocked if oil separator capillary tube temperature is low after refrigerant outlet temperature of compressor, in
driving, rises.
(
Models with 2 compressors, oil separator capillary tubes are crossing each other.)
- Conrm that is blocked in stationary state through nitrogen pressurization availability.
Breakdown of Accum Oil Return Valve (ARV)
- Damage can become cause of compressor breakdown because oil is not collected if lter of valve front/piping etc.. is blocked
with ARV is closed.
- Power connector of ARV conrms that was linked right.
- Extract connector in vacuum mode or conrm whether when insert, action sound of valve happens.
When CCH is badness, can become cause of compressor breakdown by oil foaming.