Troubleshooting
Samsung Electronics 4-53
4-3-33 : Suspension of starting due to Compressor discharge temperature sensor
/ Top temperature sensor
1.
Cause of problem
Is the resistance
value normal for the
Compressor discharge Temperature sensor/
Top temperature sensor?
(Refer toNOTE 1”)
Auto Trial Operation
Are all service valves open?
Are the Indoor Unit
and Outdoor Unit EEV normally
operating?
Are there
any blockage inside the pipe?
(filter etc.)
Check the refrigerant amount.
Replace Compressor discharge temperat
-ure sensor / Top temperature sensor
Open the Service Valve
Check the relevant EEV
Pipe inspection
Connect S-net and Manifold Gauge.
(essential requirement)
No
No
No
Yes
Yes
Yes
Yes
No
NOTE1
TOP1 : CN43 (3, 4)
TOP2 : CN45 (5, 6)
DIS1 : CN43 (1, 2)
DIS2 : CN45 (3, 4)
Resistance value
measure part
Resistance value
measure part
TOP1 TOP2
TemperatureC)Resistance(K)
130
120
100
80
60
25
20
10
0
8.9
11.2
18.5
32.0
59.0
200.0
242.0
362.0
553.0
Outdoor unit
display
Indoorunit
display
Duct, Cassette (1/2 Way),Console, Celing Cassette (4/Mini4 Way) Wall-mount ed (NeoForte)
Operation Defr ost Timer Fan Filter/MPI Operation Defrost Timer F ilter Operation Timer Turbo
×× ×
◑◑
: ON : Flash ×: OFF
Judgment
Method
When value of Compressor discharge temperature sensor / Top temperature sensor is checked at 120 or more
Cause of
problem
 Refrigerant shortage
 Electronic expansion valve is blocked.
Service valve blocked
Defective discharge temperature sensor
TOP temperature sensor defective
Blocked pipe and defective
Discharge check valve leaking on outdoor unit that is off