EasyManua.ls Logo

Samsung AM080 XV Series - Suction Temperature Sensor Error (Open;Short)

Samsung AM080 XV Series
277 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Samsung Electronics 4-43
4-3-25 Suction Temperature sensor error (Open/Short)
1.
Cause of problem
Resistance value measure part
SUCT
SUCT
No
No
Yes
Yes
Outdoor unit suction
sensor connector (CN44) connected
to PCB?
Is the resistor value matching with
NOTE1” table?
Separate the connector of the Outdoor Suction
sensor from the PCB and measure the resistance
valuebetween the 2 terminals.
Restart operation after replace the PCB.
Restart operation after connecting
the connector to PCB
Replace this part as it is the defective of the
Outdoor Suction sensor itself.
CN44 (1, 2)
NOTE1
TemperatureC)Resistance(K)
70
60
50
40
30
20
10
0
-10
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0
Outdoor unit
display
Indoorunit
display
Duct, Cassette (1/2 Way),Console, Celing Cassette (4/Mini4 Way) Wall-mount ed (NeoForte)
Operation Defr ost Timer Fan Filter/MPI Operation Defrost Timer F ilter Operation Timer Turbo
×× ×
◑◑
: ON : Flash ×: OFF
Judgment
Method
 Refer to the judgment method below.
Cause of
problem
Disconnection or breakdown of relevant sensor. (More than 4.5V or 0.5V less than)

Table of Contents

Related product manuals