Troubleshooting
Samsung Electronics 4-41
4-3-23 High Pressure sensor error (Open/Short)
1. High Pressure sensor Open/Short error determination method
1) Identifies from when power is supplied or 2 minutes after RESET, and only when set is stopped.
2) An Open/Short error will occur if the input voltage standard range of 0.5V ~ 4.95V is exc eeded .
2. Inspection Method
Replace High Pressure sensor
Please re-inspect after connecting
the connector to the PCB
No
Yes
High pressure sensor
connector (CN42) connected
to PCB?
Refill refrigerant after vacuum
No
Yes
Is there refrigerant inside the set?
(Please check by connecting the Manifold gauge
to the service valve)
Replace PCB
No
Yes
High pressure sensor
terminal of PCB : Is the voltage between
3 and 4 pins 5V?
The ف mark is the 1st pin on the PCB.
Outdoor unit
display
Indoorunit
display
Duct, Cassette (1/2 Way),Console, Celing Cassette (4/Mini4 Way) Wall-mount ed (NeoForte)
Operation Defr ost Timer Fan Filter/MPI Operation Defrost Timer F ilter Operation Timer Turbo
××◑◑◑ ×◑◑◑
●
◑◑
※ ●: ON ◑: Flash ×: OFF
Judgment
Method
Refer to the judgment method below.
Cause of
problem
Disconnection or breakdown of relevant sensor .