Key Options
Samsung Electronics 8-5
How to set the key function of the outdoor unit (cont.)
AM080ί2606XV666
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Emergency operation
for compressor
malfunction
Individual 00
0 0 Disabled (Factory default)
E560 will occur when all the
compressors are set as
malfunction state.
0 1 Set compressor 1 as malfunction state
0 2 Set compressor 2 as malfunction state
Capacity correction
for cooling
Main 0 1
00 7-9 (Factory default)
Targeted evaporation temperature
[?C] (When low temperature value
is set, discharged air temperature
of the indoor unit will decrease)
0 1 5-7
02 9-11
03 10-12
0 4 11-13
05 12-14
06 13-15
Capcity correction for
heating
Main 0 2
0 0 3.0 (Factory default)
Targeted high pressure [MPa]
(When low pressure value is set,
discharged air temperature of the
indoor unit will decrease)
0 1 2.5
0
2 2.6
0 3 2.7
0 4 2.8
05 2.9
06 3.1
0 7 3.2
0 8 3.3
Current restriction
rate
Individual 03
00 100% (Factory default)
When restriction option is set,
cooling and heating
performance may decrease
0 1 0.95
02
0.9
03 0.85
0 4 0.8
0 5 0.75
0 6 0.7
0 7 0.65
0 8 0.6
0 9 0.55
1 0 0.5
11 No restriction
Oil collection interval Main 0 4
0 0 Factory default
0 1 Shorten the interval by 1/2
Temperature to
trigger defrost
operation
Main 0 5
0 0 Factory default
0 1
Apply setting when the product is
being installed in humid area such as
near river or lake
Fan speed correction
for outdoor unit
Individual 0
6 0 0 Factory default
Silent mode for
night-time
Main 0 7
0 0 Disabled (Factory default)
Enable the silent mode for
night-time
(Itoperates automatically
depending on the temperrature.)
However, if the external contact
ineterface module(MIM-B14) is
used, entering the silent mode is
available with contact signal
0 1LEVEL 1/Auto
02 LEVEL 2/Auto
03 LEVEL 3/Auto
0 4LEVEL 1/External contact
05 LEVEL 2/External contact
06 LEVEL 3/External contact
Long-piping condi-
tion setting (Setting is
unnecessary if
high-head condition
is set)
Main
0 9
0 0 Disabled (Factory default)
0 1LEVEL 1
When equivalent length of farthest
indoor unit from the outdoor unit
is between 100~170m
02 LEVEL 2
When equivalent length of farthest
indoor unit from the outdoor unit
is over 170m
Energy saving setting
Main 1 0
0 0 Disabled (Factory default)
0 1Enabled
Energy saving mode triggers when
the room temperature reaches
desired temperature while
operating in heating mode.