Key Options
8-10 Samsung Electronics
How to check the view mode using a tact switch (cont.)
㽞AM140/160/180/200/220/240/260/280/300KXV6666
AM080/100/120/140/160/180/200/220/240/260/280/300MXVA6C
K1 control KEY operation Display on segment
Press and hold
1 time
Auto trial operation “K” “K” “BLANK” “BLANK”
K1
(Number of press)
KEY operation
Display on segment
1 time Refrigerant charging in Heating mode “K” “1” “BLANK” “BLANK”
2 times Trial operation in Heating mode “K” “2” “BLANK” “BLANK”
3 times Pump out in Heating mode (Outdoor unit address 1) “K” “3” “BLANK” “1”
4 times Pump out in Heating mode (Outdoor unit address 2) “K” “3” “BLANK” “2”
5 times Pump out in Heating mode (Outdoor unit address 3) “K” “3” “BLANK” “3”
6 times Pump out in Heating mode (Outdoor unit address 4) “K” “3” “BLANK” “4”
7 times Vacuumig (Outdoor unit address 1) “K” “4” “BLANK” “1”
8 times Vacuumig (Outdoor unit address 2) “K” “4” “BLANK” “2”
9 times Vacuumig (Outdoor unit address 3) “K” “4” “BLANK “ “3”
10 times Vacuumig (Outdoor unit address 4) “K” “4” “BLANK” “4”
11 times Vacuuming (All outdoor units) “K” “4” “BLANK” “A”
12 times End Key operation -
13 times Press and hold 1 time (Auto trial operation) “K” “K” “BLANK” “BLANK”
K2
(Number of press)
KEY operation
Display on segment
1 time Refrigerant charging in Cooling mode “K” “5” “BLANK” “BLANK”
2 times Trial operation in Cooling mode “K” “6” “BLANK” “BLANK”
3 times Pump down all units in Cooling mode “K” “7” “BLANK” “BLANK”
4 times
H/R: Checking the pipe connection
H/P: Automatic setting of operation mode
(Cooling/Heating) for trail operation
“K” “8” “BLANK” “BLANK”
5 times
Checking the amount of refrigerant
“K” “9” X X
(Display of last two digits may differ
depending on the progress)
6 times Discharge mode of DC link voltage “K” “A” “BLANK” “BLANK”
7 times
Forced defrost operation “K” “B” “BLANK” “BLANK”
8 times Forced oil collection “K” “C” “BLANK” “BLANK”
9 times Inverter compressor 1 check “K” “D” “BLANK” “BLANK”
10 times Inverter compressor 2 check “K” “E” “BLANK” “BLANK”
11 times
Fan 1 check “K” “F” “BLANK” “BLANK”
12 times Fan 2 check “K” “G” “BLANK” “BLANK”
13 times End Key operation -
K3
(Number of press)
KEY operation
Display on segment
1 time Intialize (Reset) setting Same as initial state
ఐ During "Discharge mode of DC link voltage", voltage of INV1 and INV2 will be displayed alternately.
ఐ E v en when the outdoor unit power is off, it is dangerous when you come in contact with inverter PCB and fan PCB since they are
charged with high DC voltage.
ఐ When replacing/repairing the PCB, cut-off the power and wait until the DC voltage is discharged before replacing/ repairing them.
(Wait for more than 15 minutes to allow it to discharge naturally. )
ఐ W hen there were error, 'Dicharge mode of DC link voltage' may not have been effective Especialy if error E464 and E364 have been
occured, power element might be damaged by fire and therefore, do not use the 'Discharge mode of DC link voltage'.
K1 K2 K3 K4