Key Options
Samsung Electronics 8-11
How to check the view mode using a tact switch (cont.)
㽞AM140/160/180/200/220/240/260/280/300KXV6666
AM080/100/120/140/160/180/200/220/240/260/280/300MXVA6C
K4
(Number of press)
KEY operation
Display on segment
Outdoor unit
model
SEG2, 3, 4
1 time Order frequency (Compressor 1) 1
AM160FXV6666 → Off, 1, 6
2 times Order frequency (Compressor 2) 2
120 Hz → 1, 2, 0
3 times High pressure (MPa) 3
120 Hz → 1, 2, 0
4 times Low pressure (MPa)4
1 52 MPa → 1, 5, 2
5 times Discharge temperature (Compressor 1) 5
0 43 MPa → 0, 4, 3
6 times Discharge temperature (Compressor 2) 6
87 °C → 0, 8, 7
7 times IPM temperature (Compressor 1) 7
87 °C → 0, 8, 7
8 times IPM temperature (Compressor 2)8
87 °C → 0, 8, 7
9 times
CT sensor value (Compressor 1) 9
87 °C → 0, 8, 7
10 times CT sensor value (Compressor 2) A
2 A → 0, 2, 0
11 times Suction temperature B
2 A → 0, 2, 0
12 times COND OUT temperautre C
-42 °C → -, 4, 2
13 times Temperature of liquid pipe
D
-42 °C → -, 4, 2
14 times TOP temperature (Compressor 1) E
-42 °C → -, 4, 2
15 times TOP temperature (Compressor 2) F
-42 °C → -, 4, 2
16 times Outdoor temperature G
-42 °C → -, 4, 2
17 times EVI inlet temperature H
-42 °C → -, 4, 2
18 times EVI outlet temperature I
-42 °C → -, 4, 2
19 times Main EEV1 step J
-42 °C → -, 4, 2
20 times Main EEV2 step K
2000 steps → 2, 0, 0
21 times EVI EEV step L
2000 steps → 2, 0, 0
22 times HR EEV step M
300 steps → 3, 0, 0
23 times Fan step (SSR or BLDC) N
300 steps → 3, 0, 0
24 times Current frequency (Compressor 1) O
13 steps → 0, 1, 3
25 times Current frequency (Compressor 2)P
120 Hz → 1,2,0
26 times
Suction 2 temperature (H/R) Q
120 Hz → 1,2,0
27 times Master indoor unit address R
-42 °C → -, 4, 2
28 times Address of master indoor unit S
Master indoor unit not selected → BLANK, N, D
If indoor unit No 1 is selected as the master unit → 0, 0, 1
K1 K2 K3 K4
K4 Key operation
Press and hold for
2 seconds
Check the SW version and address of the indoor units
* Display order by pressing K4 button shortly
Main - Hub - INV 1 - INV 2 - FAN 1 - FAN 2 - EEP - Automatically assigned indoor unit’s address -
Manually assigned indoor unit’s address
* Automatically assigned address
AUTO → A004 → AUTO → A005 → AUTO → C101
* Manually assigned addresses
MANU → A001 → MANU → A002 → MANU → A003