EasyManua.ls Logo

Samsung AM080 XV Series - MCU;MCU Subcooler Entrance;Exit Sensor Error (Open;Short)

Samsung AM080 XV Series
277 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Samsung Electronics 4-33
4-3-16 MCU/MCU subcooler entrance/exit sensor error (Open/Short)
1.
Cause of pr oblem
Is the sensor connector connected
on the PCB ?
Is the resistor value matching with
NOTE1” table?
Separate the connector from the PCB and
measure the resistance value
between the 2 terminals.
Restart operation after replace the PCB
Restart operation after
connecting the connector to PCB
Replace this part as it is
the defective itself.
No
No
Yes
Yes
Yes
NOTE1
TemperatureC)Resistance(K)
70
60
50
40
30
20
10
0
-10
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0
Outdoor unit
display
(MCU subcooler)
(MCU)
Indoorunit
display
Duct, Cassette (1/2 Way),Console, Celing Cassette (4/Mini4 Way) Wall-mount ed (NeoForte)
Operation Defr ost Timer Fan Filter/MPI Operation Defrost Timer F ilter Operation Timer Turbo
×× ×
◑◑
: ON : Flash ×: OFF
Judgment
Method
 Refer to the judgment method below.
Cause of
problem
MCU/MCU subcooler entrance/exit sensor is open/short

Table of Contents

Related product manuals