4-3-38 Prevention of heating / cooling operation due to outdoor temperature
Outdoor unit
display
(Prevention of heating operation due to high temperature of outdoor)
(Prevention of cooling operation due to low temperature of outdoor)
Indoorunit
display
Duct, Cassette (1/2 Way),Console, Celing Cassette (4/Mini4 Way) Wall-mount ed (NeoForte)
Operation Defr ost Timer Fan Filter/MPI Operation Defrost Timer F ilter Operation Timer Turbo
××◑◑◑ ×◑◑◑
●
◑◑
※ ●: ON ◑: Flash ×: OFF
Judgment
Method
Heating operation : When the outdoor temperature is more than 30℃
Cooling operation : When the outdoor temperature is less than -25℃
Cause of
problem
System protection operation status (Is not breakdown)
· If the outdoor temperature is satisfied the operating range, it will clear the error and start the operation automatically.